Country
Guidelines / Document along with excerpt
Link
Bangladesh
BERC (Electricity Grid Code) Regulations, 2023
The Transmission System frequency shall normally be 50.0 Hz
and shall normally be controlled in the range 49.5 – 50.5 Hz (50 Hz ± 1%).
Voltage variation on the Transmission System shall normally be ±5% for 400 kV,
±6% for 230 kV and 132 kV buses during normal operations, and ±10 % at 400 kV,
+ 10%-15% for 230 kV and 132 kV buses during emergencies.
The procedure for International Connection to the Grid and the
execution of agreement for the same shall be done by the
Licensee in consultation with the Single Buyer and the Line Ministry
India
CEA’s Technical Standards for Connectivity to the Grid
The equipment including overhead lines and cables shall comply with the relevant
Indian Standards, British Standard (BS) or International Electrotechnical
Commission (IEC) Standard, or American National Standards Institute (ANSI) or
any other equivalent International Standard.
Nepal
Nepal Electricity Grid Code 2024
Connectivity applications to be submitted to the grid owner, or the consumer service office
of the distribution utility.
Designated system planner to undertake studies.
Signing of connection agreement.